Simple Logger® II Model AL834

The Simple Logger® II Bluetooth Edition Model AL834 is a 4-channel AC current data logger with four integral flexible current sensors. Each sensor is 24 inches long and capable of wrapping around an 8 inch conductor. The AL834 has two measurement ranges of up to 300 and 3000 Amps. Both the data logger housing and the current sensors are water resistant rated to IP 65. A selection of data storage modes, as well as data sampling rates is user programmable through the free DataView® software included with the unit. Up to 1,000,000 measurements can be stored in internal nonvolatile memory. Data storage rates as fast as 8 per second are user programmable.
NOTE: Our complete catalog is not available for direct online purchase, refer to the Status Column for purchasing options. Items that do not have an Add to Cart button must be purchased from an Authorized Distributor.
Model Cat. # Description List Price Quantity/Status Distributor Stock Check
AL834 2126.14 Simple Logger® II Model AL834 $1,399.00 Out of Stock Consult Factory for Availability
ModelAL834
Cat. #2126.14
DescriptionSimple Logger® II Model AL834
List Price$1,399.00
Out of Stock Consult Factory for Availability
Print
Channels Four
Input Captive AmpFlex® AC current flexible sensors
Ranges (2) 300AAC 3000AAC
Accuracy (50/60Hz) 5 to 300A ± (1% Rdg +0.5A) 15 to 3000A (1% Rdg +1A)
Resolution 0.1AAC 0.5AAC
Sample Rate 64 samples / cycle
Storage Rate Programmable from 125ms to 1 per day
Storage Modes Start/Stop, FIFO,  extended mode (XRM) and Alarm
Recording Length 15 minutes to 8 weeks, programmable using DataView
Memory 1,000,000 measurements (2MB). Recorded data is stored in non-volatile memory and will be retained even if battery is low or removed.
Communication Bluetooth (class 2 )
Power Source 4x1.5V C alkaline batteries
Battery Life >200 hours at 125ms up to to >180 days (depending of sample rate/recording length)
Dimensions 5.9 x 5.9 x 3.57” (150 x 150 x 91mm)
Weight (With Battery) 3.9 lbs (1.77kg)
Case UL94-V0 / Case UL94-5VB
Operating Temperature 14° to 122°F (-10° to 50°C)
Storage Temperature -4° to 140°F (-20° to 60°C)
Relative Humidity Up to 85% @ 95°F (35°C) non condensing
Ingress Protection (IP) IP65 (Cover closed)
EMC EN 61326-1
Safety Compliance IEC 61010-1, EN 61010-2-32 600V CAT IV; Pollution Degree 2

User Manual

Quick Start Guide

Datasheet

Comparison Chart

Software/Firmware

DataView Software

Ver. 3.53.0013     Release Notes   |   Models Supported by DataView

IMPORTANT:

  • Back-up all template files before installation to ensure that they do not get overwritten.
  • Uninstall previous versions of DataView before installing a new version.
 

Download v3.53.0013 - English - .zip
Download v3.53.0013 - French - .zip
Download v3.53.0013 - Spanish - .zip


Supported Operating Systems:
Windows 7 (32 & 64 Bit)
Windows 8/8.1 (32 & 64 Bit)
Windows 10 (32 & 64 Bit)

Click here for the Minimum System Requirements



NOTE: PQL Loggers and Sentinel Series are no longer supported by DataView.

To obtain an older version of DataView that is compatible for these instruments, click the link below:

Download v3.09.0008 - .zip format

Supported Operating Systems:
Windows XP
Windows 7 (32 & 64 Bit)
Windows 8/8.1 (32 & 64 Bit)
Windows 10 (32 & 64 Bit)

LabView Drivers

 

  LabView Installation PDF

 
    Megohmmeters
  Ver. 1.0 Model 1060 Overview PDF
  Ver. 1.1 Models 5060 & 5070 Overview PDF
  Ver. 1.0 Models 6550 & 6555 Overview PDF
       
    Power Quality & Energy
  Ver. 1.0 Models 8333, 8435, 8335, & 8336 Overview PDF
  Ver. 1.0 Models PEL 102 & 103 Overview PDF
       
    Simple Logger II Series
 

Ver. 1.0

Simple Logger II

Overview PDF

Simple Logger® II - Firmware

  Important: To ensure that data is not lost, download all data from the instrument before installing any software and firmware updates.
       
 

Version 1.19

Release Notes
 

  1.8MB

SLII Firmware Version 1.19

01/23/17

   
SIMPLE LOGGER® II FIRMWARE

NOTE: When upgrading to version 1.19 from 1.13 or lower it is necessary to perform a “Fail Safe” upgrade.

CLICK HERE FOR UPGRADE INSTRUCTIONS
Version 1.19  pdf icon  

SOFTWARE REQUIREMENTS

To use the Simple Logger® II Firmware, you should ensure that you are using the latest version of DataView.

   
       
       

Application Notes

Forms

Technical Bulletin

Video

What's New in DataView 3.50

Model Cat. # Description List Price Quantity/Status Distributor Stock Check
2126.45 Adapter, Bluetooth USB for Simple Logger II 4-Channel Models, Models 6417, CA1510 & L452 $24.75
2133.72 Compact tool bag for field use.
12 Exterior and 14 Interior pockets
Dimensions: 13.0 x 9.8 x 9.5"
$29.95
2140.45 Replacement - Set of 12, color input ID markers for the PowerPad Series $24.50
Model
Cat. #2126.45
DescriptionAdapter, Bluetooth USB for Simple Logger II 4-Channel Models, Models 6417, CA1510 & L452
List Price$24.75
Model
Cat. #2133.72
DescriptionCompact tool bag for field use.
12 Exterior and 14 Interior pockets
Dimensions: 13.0 x 9.8 x 9.5"
List Price$29.95
Model
Cat. #2140.45
DescriptionReplacement - Set of 12, color input ID markers for the PowerPad Series
List Price$24.50

DISCOVER THE CHAUVIN ARNOUX GROUP

©2018 Chauvin Arnoux, Inc. d.b.a. AEMC Instruments. All Rights Reserved.
Contact