Ground Resistance Tester Model 6422 (Digital, 3-Point) (refurbished)

The Digital Ground Resistance Tester Model 6422 performs resistance and 3-pole ground resistance measurements. This direct reading tester is auto-ranging, so it automatically seeks out the optimum measurement range. The Model 6422 is easy to use - simply connect the leads, press to measure, and read. The large LCD also indicates low battery status and overrange.

Model 6422 comes with (3) safety color-coded terminals to aid in easy hookup and it is powered by (6) x AA alkaline batteries. The Ground Resistance Tester Model 6422 is also available in a complete Kit (150 ft).


Ground Tester | Ground Rod Tester | Earth Ground Tester | Ground Continuity Tester | Ground Wire Tester

NOTE: Our complete catalog is not available for direct online purchase, refer to the Status Column for purchasing options. Items that do not have an Add to Cart button must be purchased from an Authorized Distributor.
Model Cat. # Description List Price Quantity/Status
6422 (refurbished) 901.2135.55 Ground Resistance Tester Model 6422 (Digital, 3-Point) (refurbished) $640.00
Sale: $384.00
Model6422 (refurbished)
Cat. #901.2135.55
DescriptionGround Resistance Tester Model 6422 (Digital, 3-Point) (refurbished)
List Price$640.00
Sale: $384.00

Model 6422 - Cat. #2135.55: Includes carrying bag, (6) AA alkaline batteries (not installed) and user manual.

Model 6422 Kit (150 ft) - Cat. #2135.56: (Ground Resistance Tester Model 6422 and Test Kit For 3-Point Testing cat. #2135.35.) Includes carrying Bag, (2) 150 ft color-coded leads on spools (red/blue), (1) 30 ft lead (green), (2) 5 ft color-coded leads (red/blue), (2) 14.5 in T-shaped Auxiliary Ground Electrodes,  (1) 100 ft AEMC® Instruments Tape Measure,  (6) AA alkaline batteries (not installed) and user manual.

Print
Ground Resistance (2P Mode)
Measurement Range (0.05-99.99) Ω (80.0-999.9) Ω (0.800-9.999) kΩ (8.00-50.00) kΩ
Resolution 0.01 Ω 0.1 Ω 1 Ω 0 Ω
Intrinsic Uncertainty ± (2 % R + 10 ct) ± (2 % R + 2 ct) ±(2 % R + 1 ct) ±(2 % R + 1 ct)
Ground Resistance (3P Mode)
Measurement Range (0.50-99.99) Ω (80.00-999.99) Ω (0.800-2.000) kΩ
Resolution 0.01 Ω 0.1 Ω 1 Ω
Intrinsic Uncertainty ± (1 % R + 10 ct) ± (1 % R + 2 ct) ± (1 % R + 1 ct)
Measurement Frequency 128 Hz or 256 Hz (automatically selected)
No-load Voltage ±10 V peak
Maximum Test Current 20 mA
Measurement Mode One shot or continuous
GENERAL
Display Backlit LCD
Measurement Mode 2P (Ω), 3P (Ω)
Power Supply (6) AA Alkaline batteries
Battery Life > 2,000 x 3P earth measurements at 100 Ω
Dimensions (8.78 x 4.96 x 2.75) in (223 x 126 x 70) mm
SAFETY
Safety Ratings EMC: IEC 61326-1; IEC 61010-2-030 / 600 V CAT IV